Knob-and-tube wiring and insulation: what state programs allow
How Iowa's and Texas's weatherization programs handle insulation near knob-and-tube wiring, and what became of Seattle's 1988 standard.
On this page: 7 sections
- 1Is knob and tube wiring a hazard when a house gets insulated?
- 2Can you put insulation over knob and tube wiring in an attic?
- 3Can you insulate the walls around knob and tube wiring?
- 4What does Iowa's weatherization program require on knob and tube circuits?
- 5How does Texas decide whether to insulate an attic with knob and tube wiring?
- 6Can a weatherization program help with replacing knob and tube wiring?
- 7Does Seattle still have a rule on insulating over knob and tube wiring?
Iowa's weatherization program allows fiberglass and cellulose insulation in contact with knob-and-tube wiring only after a licensed electrical contractor certifies the wiring safe.1 In Texas's program, a hazard can potentially develop if insulation is installed without regard to knob-and-tube wiring, and insulation should be kept at least 3 inches away.2
Is knob and tube wiring a hazard when a house gets insulated?
Knob-and-tube (K&T) wiring is a wiring system usually found in older homes. K&T lines may be live and carrying an electrical load, or dead, and in Texas K&T wiring presents a challenge to the weatherization worker. Texas's weatherization program took up the question of whether to weatherize K&T homes at all, or to decline on the grounds that a future hazard may follow once attics and walls with K&T are insulated. In Texas's answer, a hazard can potentially develop if insulation is installed without regard to the K&T wiring, while a few cautionary steps during installation let the house's thermal boundary be significantly improved and safeguard the home from possible hazards. Whether the K&T wiring is live or dead should be determined at the start and documented in the whole house assessment. Texas weatherization staff should also stress to the client that during future activity in the attic, such as repairs or storage, care should be taken to keep insulation and foreign objects away from the wiring.2
Can you put insulation over knob and tube wiring in an attic?
In Iowa's program, attics with active knob-and-tube wiring may be treated in one of two ways, based on the work order. At agency discretion, a licensed electrical contractor may inspect and certify all the K&T wiring to be safe, and in those cases fiberglass and cellulose insulation are acceptable in contact with the wiring and the attic may be fully insulated. Iowa's knob-and-tube wiring that a licensed electrician hasn't certified safe has the wiring isolated instead: live K&T in that case will not be covered or surrounded, and a dam that does not cover the top separates the insulation from the wire path.1
In Texas's guidance, an insulation baffle or "insulation dam" can be constructed to avoid covering the K&T with insulation, whether fiber or cellulose is used.2 Iowa's standard for uncertified wiring calls for a dam of un-faced fiberglass batts at least 14 inches wide and equivalent to R-38 to keep attic insulation from covering the wiring, and where the wiring runs above the joists, an un-faced fiberglass batt at least 6 inches wide must be installed below the wiring. Where Iowa's K&T goes through the joists, no insulation goes below the wiring and only the dam is built, and the balance of the attic may be blown to the required insulation depth without covering any knob and tube.1 In Texas, care should be taken during installation to keep insulation 3 inches minimum from the K&T wiring, and the Texas field guide has the fiberglass batts installed to leave 3 inches of clearance around the knob-and-tube components.2
The table covers Iowa's and Texas's weatherization programs; other states and programs have their own rules.
| Program | Attic with K&T wiring | Walls with live K&T wiring | Source |
|---|---|---|---|
| Iowa weatherization | Fully insulated if a licensed electrician certifies the wiring safe; uncertified wiring is isolated behind a dam of un-faced fiberglass batts | Fully insulated if a licensed electrician certifies the wiring safe; not insulated if uncertified | Iowa HHS, Bureau of Weatherization: Iowa Weatherization Program Notice 15-01, read November 25, 2026 |
| Texas weatherization | Insulated only where the net R-value works out at R-11 or above, with insulation kept 3 inches from the wiring | Wall cavities containing live K&T are not insulated | Texas Department of Housing and Community Affairs: Knob and Tube (K&T) Wiring & Priority List, read November 25, 2026 |
Can you insulate the walls around knob and tube wiring?
In Iowa, walls with active knob-and-tube wiring may be treated in one of two ways, based on the work order. Where a licensed electrician certifies the wiring safe, fiberglass and cellulose insulation are acceptable in contact with the K&T and the walls may be fully insulated, while Iowa sidewalls with active knob-and-tube wiring that a licensed electrician hasn't certified safe will not be insulated.1
Texas's Department recommends not insulating walls that have live K&T in them. Insulating some stud bays while leaving the bays that contain K&T uninsulated tends to cause moisture issues in the wall structure, and the reduction in total R-value may not be cost effective. The Texas Weatherization Field Guide puts the wall rule in one line: "Do not insulate wall cavities containing live knob & tube wiring systems".2
What does Iowa's weatherization program require on knob and tube circuits?
Iowa's weatherization standards require S-type fuses in homes with knob-and-tube wiring to provide over-current protection, unless local codes prohibit them. If S-type fuses will not work because of overloaded circuits, a new service panel must be installed and the house brought up to code, and Iowa agencies may use either General Health and Safety Repair funds (within limits) or a pilot project to complete that work. Iowa's attic insulation standard lists the same requirement for houses with knob-and-tube wiring: they must have S-type fuses installed to provide over-current protection, and the client is to be told the importance of properly fused circuits. All Iowa houses evaluated April 10, 2015 and after are completed using the revised Iowa Weatherization Standards and Field Guide Manual that DOE approved on April 9, 2015.1
How does Texas decide whether to insulate an attic with knob and tube wiring?
In Texas's weatherization program, whether a house with K&T wiring should be insulated can't be guessed: the formulas must be run to determine if the net R-value is at or above R-11. The net R-value is the R-value of the attic floor insulation as a whole, once the strips left uncovered along the wiring are counted in. Texas bases the attic decision on the heat transmission formula and the net R-factor determination, and the calculations and resulting decision must be included in the house file.2
In the Texas Example A, a 30 by 30 attic floor with 2 strips of K&T down the middle and R30 insulation over the covered area drops to R12.7, which is R-11 or above, so the work continues. The same house with a third uninsulated line drops below R-11 to an overall R-value of 7.5, and that attic would not be insulated. A larger attic floor area raises the R-value to the cut-off: Example C nets R11.11 with the same 3 strips of K&T.2
Can a weatherization program help with replacing knob and tube wiring?
The Texas Weatherization Field Guide suggests K&T replacement where possible. Where the cost of rewiring a home is excessive, Texas WAP subrecipients may cost effectively insulate the attic, blowing insulation into the remaining areas with fiberglass batts acting as a dam that keeps it away from the wiring. Some regions may have rehabilitative programs that may allow K&T wiring replacement, and Texas recommends checking your community's programs to see if assistance is available in your region. In Texas, knob-and-tube wiring is not a reason to disqualify a homeowner from the weatherization program, though weatherizing a K&T home is a specific task requiring an understanding of how to keep insulation away from the K&T wiring while the rest of the home is weatherized.2
Does Seattle still have a rule on insulating over knob and tube wiring?
Seattle's Director's Rule 34-88 set "Standards for Protecting Knob-and-Tube Wiring when Thermal Insulation is Installed" and took effect on June 1, 1988. The rule interprets Seattle's Building Code (Ch 22.100), and its status today is Rescinded, by rule 10-92. Seattle's Tips, Director's Rules and other guidance documents may not reflect current regulations or requirements, due to interim regulations implementing state legislation effective July 2025 and pending changes to the Design Review program and the local codes implementing State Environmental Policy Act (SEPA) requirements. For a specific code question or permit application in Seattle, the Department of Construction and Inspections takes questions through its Send Us a Question website.3
Iowa's Weatherization Program Notice 15-01, the Texas Department of Housing and Community Affairs' knob and tube guidance and Seattle's Director's Rule 34-88, checked November 2026.
Sources (3)
- Iowa HHS, Bureau of Weatherization: Iowa Weatherization Program Notice 15-01, read November 25, 2026 ↑
- Texas Department of Housing and Community Affairs: Knob and Tube (K&T) Wiring & Priority List, read November 25, 2026 ↑
- Seattle Department of Construction and Inspections: DR 34-88, Standards for Protecting Knob-and-Tube Wiring when Thermal Insulation is Installed, read November 25, 2026 ↑